Palazzoli

DELPHYS GP 2.0 160-1000kVA

 

Sn (kVA) 160 200 250 300 400 500 600 800 1000
Pn [kW] 160 200 250 300 400 500 600 800 1000
Input / output 3/3
Parallel configuration up to 4 MW
Input
Rated voltage 400 V 3ph
Voltage tolerance 200 V to 480 V(1)
Rated frequency 50 / 60 Hz
Frequency tolerance ± 10 Hz
Power factor/THDI > 0.99 / < 2.5%(3)
Output
Power factor 1 (according to IEC/EN 62040-3)
Rated voltage 3ph + N 400 V
Voltage tolerance static load ±1% dynamic load in accordance with VFI-SS-111
Rated frequency 50 / 60 Hz
Frequency tolerance ± 2% (configurable for GenSet compatibility)
Total output voltage distortion - linear load ThdU < 1.5%
Total output voltage distortion - non-linear load (lEC 62043-3) ThdU < 3%
Short-circuit current(2) up to 3.4 x In
Bypass
Rated voltage rated output voltage
Voltage tolerance ± 15% (configurable with from 10% to 20%)
Rated frequency 50/60 Hz
Frequency tolerance ± 2% (configurable for GenSet compatibility)
Efficiency
Online mode @ 40 % of load up to 96%
Online mode @ 75 % of load up to 96%
Online mode @ 100 % of load up to 96%
Fast EcoMode up to 99%
Environment
Operating ambient temperature from 0 °C up to +40 °C(1) (from 15 °C to 25 °C for maximum battery life)
Relative humidity 0% - 95% without condensation
Maximum altitude 1000 m without derating (max. 3000 m)
Acoustic level at 1m (ISO 3746) <65 dBA <67 dBA <70 dBA <72 dBA <74 dBA
UPS Cabinet
Dimensions W x D x H 700 x 800 x 1930 mm 1000 x 950 x 1930 mm 1400 x 800 x 1930 mm 1600 x 950 x 1930 mm 2800 x 950 x 2060 mm 3510 x 950 x 2060 mm 3910 x 950 x 2060 mm
Weight 470 kg 490 kg 850 kg 900 kg 1000 kg 1500 kg 2300 kg 2800 kg 3850 kg
Degree of protection IP 20 (other IP as option)
Colours cabinet: RAL 7012, door: silver grey
Standards
Safety IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2
EMC IEC/EN 62040-2, AS 62040.2
Performance IEC/EN 62040-3, AS 62040.3
Seismic compliance(4)
Uniform Building Code UBC-1997, EN 60068-3-3/1993 (seismic),
EN 60068-2-6/2008 (sinusoidal), EN 60068-2-47/2005 (mounting)
Product declaration CE, RCM (E2376)

(1) Conditions apply.

(2) Worst condition (Auxiliary Mains not available).

(3) With input THDV < 1%.

(4) 160, 200 and 500 kVA/kW models.